This UV/IR flame detector is constructed by combining Ultraviolet Sensor that has spectral response range from 185nm to 260nm and Infrared Sensor that senses Infrared ray wavelength of 4.3§
|
|
|
Our Products
UV/IR Flame Detector
|


 |
 |
This UV/IR flame detector
constructed with high sensitive sensors and sophisticated software
programmed to detect immediately and accurately the UV/IR wavelengths
of heat and flames caused by fire. This detector is addressable and
can be networked to send out visual signals, sound alarm signals,
and to activate automatic extinguishing systems through output terminal
of the detector or through control circuit when the detector senses
UV/IR wavelengths of fire or flame.

Petrochemical Plants, Vehicle Coating/Painting Factories, LNG/LPG
Storages, Tankers/Oilers, Semi-conductor Facilities, Power Plants
(Atomic, Hydraulic/Thermoelectric, Cogeneration), Substation/Transmission
Facilities, Parking Towers, Broadcasting Communication Facilities,
Iron-Works Facilities, Research Laboratories, and Other facilities/equipments/areas
that has fire breaking-out possibilities.
|
 |
 |
 |
| minimizing fault detection
(sunlight and other non-fire sources) |
 |
- Real time monitoring
of product status by RS-485 data communication
- Event data can be recorded and accumulated |
 |
| The product assures high
reliability by acquiring various quality certification and is an eco-friendly
product by reducing the effects of EMI and EMC. |
 |
| by dual sensing circuit of UV and IR |
 |
| by adopting high sensitive
sensors |
 |
 |
| RS-485 data communication,
relay contact output |
 |
| providing convenience
for installation work |
|
 |
 |
| MODEL NAME |
CS-UIEX-11 |
| Dimension |
75(mm) X 58(mm) |
| Weight |
Appx. 0.5 Kg |
| sensing range |
Max 45M |
| Enclosure material |
Aluminum Diecasting |
| Operating Temperature range |
-40¡É ~ + 80¡É |
| Humidity range |
RH 0% to 85% |
| Field of View |
100° |
| Operating voltage |
DC 24 V ± 20 % |
| Power consumption |
Max. 40mA in standby, Max. 85mA in alarm |
| LED Indication |
Alternate blinking of Red, Green, and Blue
LEDs for about 9 seconds when power is on initially. Green LED
is continuously ON during normal standby state. Red LED is continuously
ON in ALARM state. |
| Relay Outputs |
1A at 30V DC, 0.5A at 125V AC |
| Explosion proof |
Ex d IIC T6 |
| Water and Dust |
IP66 |
|
 |
|