fire extinguishing system, flame detectors, fire detectors
CS-UIEX-01 Flame Detector combines the
UV sensor that perceives UV wavelength
characteristic (185-260nm) and the IR sensor that perceives IR wavelength characteristic (4.3§­) so the UV/IR Flame Sensor has been organized.

Our Products

Flame Detector

Flame Detector
Flame Detector

Flame Detector

As fire is a combustion phenomenon that a material gets burned with light, heat, and/or flame within the air or oxygen, generally, it means such burning phenomenon creating heat, smoke, and flame. Especially, the flame shows such unique combustion feature from the beginning of the fire. Among these features, there is such wavelength range existing differently each other between UV (Ultraviolet Rays) and IR (Infrared Rays) that is not able to be recognized by human eyes.
CS-UIEX-01 Flame Sensor combines the UV sensor that perceives UV wavelength characteristic (185 ~ 260nm) and the IR sensor that perceives IR wavelength characteristic (4.3§­) so the UV/IR Flame Sensor has been organized. Since UV/IR Flame Sensor perceives only narrow wavelength bandwidth as the above, such errors and malfunction for other various non-fire factors in the surroundings have been minimized. Also, because high sensitivity sensor is used, the maximum sensitivity with the minimum current consumption has been realized. As the function to recognize fire flame has been enhanced, such reliability of fire detection has been improved.
Also, current output (0-20mA) and serial (RS-485) communication output are possible in order to possibly organize network. As such remote control module has been equipped inside the sensor firstly in Korea, it is easy to check the status of operation and contamination on the spot so maintenance is also easy.
.

¤ýThe areas that require UV-IR fire/flame detector
Petrochemical Plants, Vehicle Coating/Painting Factories, LNG/LPG Storages, Tankers/Oilers, Semi-conductor Facilities, Power Plants (Atomic, Hydraulic/Thermoelectric, Cogeneration), Substation/Transmission Facilities, Parking Towers, Broadcasting Communication Facilities, Iron-Works Facilities, Research Laboratories, and Other facilities/equipments/areas that has fire breaking-out possibilities.

A. Accurate Fire Perception
Malfunction and error for other light sources have been minimized since time delay data and sensitivity upon the size of flame in case of fire have been programmed inside the MICOM.
B. Fast Response for Fire
Based on use of high sensitivity UV/IR sensor, response is fast.
C. No Influence from Environmental Factor
It is not influenced by snow, rain, fog, temperature, and humidity.
D. Convenient Control of Response Time and Sensitivity upon Distance and Size of the Fire
It is possible to easily control/adjust using PWM switch inside the sensor.
E. Convenience of Installation and its Location
It is possible to set up various ranges to perceive based on the compact design and such free conversion of the directions as upper, lower, right, and left.
It is also possible to select various locations to install such as ceiling and corner of walls.
It is convenient for additional installation and management.
F. Convenience of Maintenance
It is easy to check any problem of the product based on the self-diagnosis function. Since it is also possible to check the status of the sensor through remote control, such maintenance is easy.
G. Communication Circuitry
Since the serial communication circuitry (RS-485) is equipped, it is possible to confirm the self diagnosis function through Micom. Also, if such network through program is organized, it is possible to promptly grasp various information such as location, current status, individual product history, and operation history of the sensor. (Optional)
H. Compatibility with the Existing Reception set
It is compatible with R-type and P-type reception set that are currently distributed in the market.
I. Convenience of Additional Installation and Management
±¹It is easy to consult about specification change and A/S all the time as it is a domestic product.
J. Structural Stability (Explosion-Proof Performance Verified)
It does not externally provide any cause for fire based on internal pressure explosion-proof structure. (explosion-proof rate: Exd ¥±C T6)
MODEL NAME CS-UIEX-01 CS-UI-01
Dimension 120 ¡¿130 ¡¿115§® 79 ¡¿87 ¡¿90§®
Weight (Main body) 2200g 1500g
Detect Distance 25M 25M
Explosion-proof Construction Exd¥±C T6 Normal (Non explosion-proof)
Material Aluminum-Casting Powder Coating
Operating Temperature -40¡É ¡­ +80¡É
Operating Humidity RH 85 %
Place to install Should be installed in such places that the efficiency of watch can be maximized inside the building
(Ex: Wall, Ceiling, Wall-corner)
Visual Angle 90¡Æ (Left/Right 45¡Æ)
Rated Voltage DC 24 V ¡¾ 20 %
Consuming Current Standby: 17§Ì, UV Alarm: 90 §Ì, IR Alarm: 56§Ì
LED COLOR Standby: Green LED light-on, Alarm: Red LED light-on
Contact Point output / capacity When alarming for fire, / 10A / 125V AC
Current output signal range 0 - 20 §Ì (Option for signal)
Csa bestouch | Heat detector | Fire detectors | Thermo controller | Flame detectors | Automatic fire extinguisher | Fire extinguishing system | Linear heat detector | Ccfl